Exhibition | Home | Contact Us | Downloads
FREE QUOTATION

Products & Systems

Solid Floor
Suspended Floor
Battened Floor
Floating Floor
UFH Pipe
Manifolds
UFH Control System
One Room System

The installation descriptions above are summaries only and should not be taken as full installation specifications.

With all Underfloor Heating Systems, the pipe loops must be filled and under pressure during any floor laying process. During periods where there is a risk of freezing, special precautions must be taken.

Solid Floor

These are suitable for a wide range of floor coverings and construction methods. The system is simple and straightforward to install. The most widely used underfloor heating system, performing in ooo's of homes countrywide.

Due to the high thermal mass, this system has a relatively slow thermal response, but this is largely overcome by using individual room control and close set-back temperatures.

Installation

  • Edge insulation (client to supply) should be fitted against external walls to avoid cold bridging and to allow for expansion of the screed
  • Floor insulation is laid on flat level floor
  • The Pipe Rail is stapled to the floor insulation using plastic staples, at approx. 1.5m centres. The pipes are clipped into the pipe channel at the centres specified in the design.
  • Once the system of loops has been filled and pressure tested, the conventional sand cement screed (65mm min depth) or proprietary flowable screed can be laid.
  • Once the screed has been fully cured, the system can be commissioned.
  • The designed flow temperature is 45°C with maximum heat output of 100 watts/sq.m
 
SELF BUILDERS: Background to Underfloor Heating, Products & Systems, Guarantees, FAQ's, Case Histories Self Builders
HEATING & PLUMBING INSTALLERS: Products & Systems, Exhibitions, Downloads, Case Histories Heating & Plumbing
Installers
SPECIFIERS: Products & Systems, Case Histories, FAQ's Specifiers
Products & Systems
Case Histories
FAQ'S
LINKS Links